5.1 Overview
Hebel PowerWall basically consists of Hebel PowerPanel secured to the framing via horizontal steel top hats. This section provides the basic information on the selection of top hat spacings for a given stud spacing and wind category, as well as considerations to assist the designer in determining the appropriate wall configuration.
The design information presented in Table 5.1 to 5.5 has been determined for the following top hat types:
- Rondo 303 – Rondo Building Services Pty Ltd.
- Lysaght Topspan 22 – Bluescope Steel Ltd.
- FastStud 24TH42.
For other brands or types of top hats, contact the manufacturer for design information. Minimum performance requirements for the metal studs, top hats, fixings and Hebel PowerPanel have been provided to assist the designer.
IMPORTANT
The design and approval of the structural framing (cold-formed steel or timber) is to be provided by the framing product manufacturer and/or project engineer.
5.2 Principles of Design
The principles on which the design is based include:
a) The lateral wind loads applied to the PowerPanels are transferred into the horizontal top hats, then to the stud frame, which should be designed in accordance with the relevant Australian Standards for the imposed loads. The frame should be designed for all bracing and hold down requirements.
b) The design of the stud frame shall consider the weight of suspended PowerPanels (such as the upper storey of two-storey construction).
c) The system is not considered as cavity construction, as the top hat clearly bridges the cavity, hence the details show the necessity of sealing the windows and door frames, as well as applying a water resistant external coating.
d) The system specifications vary with wind load. The notation used in AS1684 Residential Timber Framed Construction has been adopted.
e) The localised effects of wind around corners of buildings have been considered in the design and included in the tables. The extent of this effect is discussed towards the end of this section.
Criteria for Corner Panels
Due to the increase of wind load around the corners of buildings, extra top hats and screws may be necessary (N3 and greater) for a distance of 1200mm in each direction from the corner.
Tables 5.1 to 5.5 identify the installation criteria in these areas, in the columns titled ‘Panel Location – Corner’.
Cyclonic Loading Effects
Hebel PowerWall for Detached Houses & Low Rise Multi-Residential External Walls has been tested at the James Cook Cyclone Structural Testing Station (Repor t No. T5 444) in Townsville. The pullout capacity of the screw into the back of the Hebel PowerPanel is the critical element in the design. The results from the cyclic testing showed that the system, in par ticular the pullout load of the screw, is unaffected by the cyclic loading. The detailing presented in this design guide is satisfactory for cyclonic areas.
Earthquake Loads
Earthquake loading has not been considered in this design guide.
5.3 Design Tables
This section presents tables to assist the designer in the selection of the number of top hats and number of screws for securing the Hebel PowerPanel to the framing, for a given wind category.
IMPORTANT
The wind category is to be used as a guide. The designer should check the project wind pressure against the valves given in the tables.
Panels Supported at Base
Table 5.1 Number of Top Hats – Panel Supported at Base (such as slab edge or shelf angle)
Wind
Category |
Maximum
Permissible
Suction
Wind
Pressure
(kPa) |
Stud Spacing
(mm) |
Number of Top Hats Per Panel |
| Panel Length (mm) |
| 2400 |
2550/2700 |
2850/3000 |
| Panel Location |
Panel Location |
Panel Location |
| Typical |
Corner |
Typical |
Corner |
Typical |
Corner |
| N2 |
0.42 |
600 |
3 |
3 (4) |
3 |
3 (4) |
4 |
4 |
| N3 |
0.66 |
600 |
3 |
3 (4) |
3 |
4 |
4 |
4 |
| N3, C1 |
0.66 |
450 |
3 |
3 (4) |
3 |
3 (4) |
4 |
4 |
| N4, C2 |
0.98 |
450 |
3 (4) |
4 (5) |
3 |
4 (5) |
4 |
5 (6) |
| N5, C3 |
1.40 |
450 |
4 (5) |
4 (6) |
5 |
5 (6) |
5 |
5 (7) |
Note:
1. Figures shown in brackets are the top hats required when using RONDO 303 top hats.
2. All top hats to be spaced evenly, with top and bottom top hats installed 150mm (typical) from the end of the PowerPanel.
3. Additional top hats will be required below all window openings and above openings if a PowerPanel or sill block is to be installed in this location.
4. Corner panel location applies to PowerPanels within 1200mm of corners. Permissible wind pressures have been increased by a factor of 2 in these PowerPanel locations.
Table 5.2 Number of Screws Per Panel at Each Top Hat Location – Panel Supported at Base (such as slab edge or shelf angle)
Wind
Category |
Maximum
Permissible
Suction
Wind
Pressure
(kPa) |
Stud Spacing
(mm) |
Number of Screws Per Panel Per Top Hat |
| Panel Location |
| Typical |
Corner |
| Top Hat Location |
Top Hat Location |
| Ends |
Middle |
Ends |
Middle |
| N2 |
0.42 |
600 |
2 |
2 |
2 |
2 |
| N3 |
0.66 |
600 |
2 |
3 |
2 |
3 |
| N3, C1 |
0.66 |
450 |
2 |
2 |
2 |
3 |
| N4, C2 |
0.98 |
450 |
2 |
3 |
2 |
3 |
| N5, C3 |
1.40 |
450 |
2 |
3 |
3 |
4 |
Note:
1. For fire rated construction a minimum of 3 screws per middle top hat is required (FRL 240/180/180 for a fire source from the PowerPanel side of the wall only).
2. Type of screw used is the 14-10x65mm Hex Head Type 17 screw, fixed from inside the building, or 14-10x100mm MP Bugle Head Batten screw, fixed from outside the building (as per Table 5.6).
3. Corner panel location applies to PowerPanels within 1200mm of corners. Permissible wind pressures have been increased by a factor of 2 in these PowerPanel locations.
Panels Suspended from Frame
Table 5.3 Number of Screws Per Panel at Each Top Hat Location – Panel Suspended at Gable Ends
| Wind Category |
Maximum Permissible Suction Wind
Pressure
(kPa) |
Stud Spacing(mm) |
Number of Screws Per Panel Per Top Hat |
Maximum Spacing of Top Hat(mm) |
| Panel Location |
Panel Location |
| Typical |
Corner |
Typical |
Corner |
| N2 |
0.42 |
600 |
2 |
3 |
800 |
800 |
| N3 |
0.66 |
600 |
3 |
4 |
800 |
650 |
| N3, C1 |
0.66 |
450 |
3 |
4 |
800 |
650 |
| N4, C2 |
0.98 |
450 |
4 |
4 |
800 |
450 |
| N5, C3 |
1.40 |
450 |
4 |
4 |
600 |
350 |
Note:
- Top and bottom top hats installed 150mm (typical), and 250mm (max.) from the end of the PowerPanel.
- Top hats to be installed horizontally with PowerPanels to span ver tically. Number of Screw Per Panel Per Top Hat Information is not suitable for soffits or any other areas where the PowerPanel is not ver tical.
- Corner panel location applies to PowerPanels within 1200mm of corners. Permissible wind pressures have been increased by a factor of 2 in these PowerPanel locations.
Table 5.4 Number of Top Hats – Panel Suspended from Framing (such as, second storey construction)
Wind
Category |
Maximum
Permissible
Suction
Wind
Pressure
(kPa) |
Stud Spacing
(mm) |
Number of Top Hats Per Panel |
| Panel Length (mm) |
| 2400 |
2550/2700 |
2850/3000 |
| Panel Location |
Panel Location |
Panel Location |
| Typical |
Corner |
Typical |
Corner |
Typical |
Corner |
| N2 |
0.42 |
600 |
4 |
4 |
4 |
4 |
4 |
4 |
| N3 |
0.66 |
600 |
4 |
4 |
4 |
4 |
4 |
4 (5) |
| N3, C1 |
0.66 |
450 |
4 |
4 |
4 |
4 |
4 |
4 (5) |
| N4, C2 |
0.98 |
450 |
4 |
4 (5) |
4 |
4 (6) |
4 |
5 (6) |
| N5, C3 |
1.40 |
450 |
4 (5) |
5 (6) |
5 |
6 (7) |
5 |
6 (8) |
Note:
1. Figures shown in brackets are the top hats required when using RONDO 303 top hats.
2. All top hats to be spaced evenly, with top and bottom top hats installed 150mm (typical) from the end of the PowerPanel.
3. Additional top hats will be required below all window openings and above openings if a PowerPanel or sill block is to be installed in this location.
4. Corner panel location applies to PowerPanels within 1200mm of corners. Permissible wind pressures have been increased by a factor of 2 in these PowerPanel locations.
Table 5.5 Number of Screws Per Panel at Each Top Hat Location – Panel Suspended from Framing (such as, second storey construction)
Wind
Category |
Maximum
Permissible
Suction
Wind
Pressure
(kPa) |
Stud Spacing
(mm) |
Number of Screws Per Panel Per Top Hat |
| Panel Location |
| Typical |
Corner |
| Top Hat Location |
Top Hat Location |
| Ends |
Middle |
Ends |
Middle |
| N2 |
0.42 |
600 |
2 |
2 |
2 |
3 |
| N3 |
0.66 |
600 |
2 |
3 |
3 |
4 |
| N3, C1 |
0.66 |
450 |
2 |
3 |
3 |
4 |
| N4, C2 |
0.98 |
450 |
2 |
4 |
3 |
4 |
| N5, C3 |
1.40 |
450 |
2 |
4 |
3 |
4 |
Note:
1. For fire rated construction a minimum of 3 screws per middle top hat is required (FRL 240/180/180 for a fire source from the PowerPanel side of the wall only).
2. Type of screw used is the 14-10x65mm Hex Head Type 17 screw, fixed from inside the building, or 14-10x100mm MP Bugle Head Batten screw, fixed from outside the building (as per Table 5.6).
3. Corner panel location applies to PowerPanels within 1200mm of corners. Permissible wind pressures have been increased by a factor of 2 in these PowerPanel locations.
5.4 Stud Frame
The stud frame shall be designed by the steel stud manufacturer or appropriate project engineer. Hebel PowerPanel is a masonry product and the support structure should be designed to provide sufficient stiffness.
The steel stud frame shall be designed and constructed in accordance with AS3623 and AS/NZS4600 (BCA Performance Requirement) with performance requirements for the studs of:
Properties:
- Cold-formed steel studs.
- Minimum yield strength 300MPa
- Minimum thickness 0.75mm BMT.
- Coating class Z275 (see Durability).
- The designer shall specify the need for noggings.
5.5 Steel Top Hat
Other steel top hats than those referenced in this design guide shall be designed by the top hat manufacturer or appropriate project engineer.
The steel top hats shall be designed and constructed in accordance with AS3623 and AS/NZS4600 (BCA Performance Requirement) with performance requirements for the top hats, of:
Properties:
- Cold-formed steel top hats.
- Minimum thickness 0.42mm BMT.
- Minimum yield strength 300MPa.
- Coating class Z275 (see Durability).
Alternate steel top hats must have an equivalent or better performance than the top hat products outlined in Section 5.1.
5.6 Hebel PowerPanel
Design procedures for the verification of wall systems consisting of Hebel autoclaved aerated concrete (AAC) PowerPanels generally follow the design principles outlined in Australian Standard AS3600 – Concrete Structures, with the exception of cover requirements for durability and development length for reinforcement.
The strength design of the Hebel PowerPanels has been carried out using the Transformed Section Theory, as detailed in the text book, ‘Reinforced Concrete’ by Warner, Rangan and Hall (Longman Cheshire). The load carrying capacity of the Hebel PowerPanel is influenced by several factors, such as:
- Imposed action (wind).
- Lateral stiffness of the supporting structure (lightweight structural (cold-formed) steel framing).
• Stud size and spacings.
• Deflection limit.
- Height of the wall.
- Number and spacing of the top hats.
- Number of screw fixings considered effective.
5.7 Fixings
Table 5.6 outlines the connection type and requirements for constructing Hebel PowerWall detailed in this design guide. The project engineer or framing manufacturer is responsible for specification of alternative details. The minimum performance requirement of the screw is:
- Minimum screw coating class in accordance with AS3566: Class 3. (Refer Section 6.0 for Durability).
Table 5.6 Screws Types
| Type of Screw |
Application |
Top Hat Type |
Socket Type |
| 12-11x25mm Hex HeadType 17 screw |
Fix top hat to timber frame |
Rondo 303Lysaght TopSpan 22FastStud 24TH42 |
5/16” Hex Mag. Socket |
| 10-16x16mm Hex Headself drilling screw |
Fix top hat to steel stud frame(1.2mm BMT max.) |
Rondo 303Lysaght TopSpan 22FastStud 24TH42 |
5/16” Hex Mag. Socket |
| 14-10x65mm Hex HeadType 17 screw |
Fix PowerPanel to top hatfrom inside of building |
Rondo 303Lysaght TopSpan 22FastStud 24TH42 |
3/8” Hex Mag. Socket |
| 14-10x100mm MP Bugle HeadType 17 screw |
Fix PowerPanel to top hatfrom outside of building |
Rondo 303Lysaght TopSpan 22FastStud 24TH42 |
5mm Hex drive bit 50mm long |
5.8 Design Considerations
5.8.1 Structural Framing Design
The use of Hebel PowerWall in two-storey construction involves a number of design issues that require attention. In conjunction with the following, refer to the Construction Details in Section 17.3 & 17.7.
Note, when PowerPanels are suspended from the stud frame the project engineer shall design the frame to support the weight of the PowerPanels.
Design Tip
In order to reduce the load of the upper storey PowerPanels and make installation easier, the lower storey PowerPanels should be specified as 2700mm/3000mm in length and the upper storey PowerPanels as 2400mm in length. The vertical dimensions can be adjusted to suit.
A garage is considered ‘attached’ when at least one full side of the garage is connected to the main dwelling.
5.8.2 Two Storey Construction
Steel Frame Construction
Two storey construction suits a steel framed dwelling as the weight of the upper storey PowerPanels bear directly on the lower storey PowerPanels. Note, lower storey PowerPanels are to bear on the slab. However, consideration should be given to the sectional size of the lintels over openings on the lower storey.
As the details reveal, only an ‘Ableflex’ joint is required at the horizontal PowerPanel junction between the upper and lower PowerPanels.
Timber Frame Construction
In contrast, the upper storey PowerPanels™ cannot rest on the lower storey PowerPanels™ in timber framed dwellings, due to the effects of timber shrinkage. Movements in the order of 25mm can occur in a two storey timber frame with a timber first floor. The fixing method used in Hebel™ PowerWall™ does not allow for this extent of differential movement between the external skin and the timber frame.
The allowances for shrinkage of timber framing in BCA 2006 Vol. 2, Section 3.3.1.10, by providing gaps between framing and masonry, should be adopted as a minimum.
It is therefore recommended that the upper storey PowerPanels™ be installed 35mm clear of the lower storey PowerPanels™. During construction a temporary packer is used to separate the PowerPanels™ and is then removed after the PowerPanels™ have been screwed to the top hats.
The impact of this construction is to load the lower storey frame with the weight of the upper storey PowerPanels™. In effect, an extra 51kg/m2 (for the weight of the upper PowerPanels™) is being added to the load already carried by the timber frame. The load approximates 1.2 kN/m (2.4m PowerPanel™).
To simplify the design implications of this extra load, it is recommended to add an extra 1.4m of tributary width for a 90kg/m2 Tile Roof load (for 2.4m long upper PowerPanels™) for the design of the lower storey frame and timber lintels, when using AS1684. The support of the full weight of the upper storey PowerPanels™ can be adequately supported by the top hat system. A full design using a safety factor of five has been undertaken and checked to confirm this. The number of top hats can be determined in Table 5.4 to support the suspended PowerPanels™, and the PowerPanels™ screw fixed as per Tables 5.5.
5.8.3 Secondary Support Framing
There is a need for secondary support framing when:
The layout of the main structural framing does not allow this framing to be used as a support. In this case a mullion is required to break up the span of the PowerPanel™, or cleats provided to act as support and connection points for the PowerPanels™.
Around openings: the PowerPanels™ adjacent to the opening may not have sufficient capacity or stiffness to resist the additional loads that are re-distributed from the opening and infill PowerPanels™.
In this case angles are required to transfer the loads from the opening (window) and infill PowerPanels™ back to the main structural framing.
5.8.4 Bracing of the Building
The walls of the dwelling should be braced using steel cross bracing wherever possible, to allow the fixing of the PowerPanels™ from inside the building, such as Teco Speed Bracing. Ply or sheet bracing should be used on the external wall, if the walls are too short for the steel cross bracing (Refer AS 1684-1999). In this case, the full length of the wall should be sheeted to prevent misalignment of the PowerPanels™.
Alternatively, localised strips of the sheeting can be fixed to the intermediate studs, between the areas of full sheet bracing, to maintain the PowerPanel™ alignment. The PowerPanels™ to be installed over the areas of full plywood sheeting will need to be fixed from the outside of the building using the 100mm long Bugle Head Batten screw (Refer Table 5.6). The extent of the bracing should be determined by the timber frame designer or project engineer.
NOTE
CSR™ Hebel™ does not recommend fixing Hebel™ PowerPanels™ from the inside when sheet bracing is installed. If sheet bracing is used over steel or timber frame construction then increase the length of the screw fixing the top hat to the stud by the thickness of the sheet bracing (refer to Section 5.7).
